Some expert witnesses are confused by the terms "permeable" & "waterproof" as they relate to concrete.
Waterproof VS Permeability
Increased
concrete densities provide for stronger structures, for which I am an
advocate. However, increased densities ONLY REDUCE concrete's permeability, they DO NOT
render it impermeable (waterproof).
Experts need to stop claiming that
higher psi concrete's are WATERPROOF - THEY ARE NOT ! Yes, they
ARE less permeable, but water will still weep through the concrete - just
at a slower rate.
None of the following references (all in my personal library) state that higher density concretes are waterproof:
Building Code Requirements for Structural Concrete (ACI 318M-08)
Steel Reinforced Concrete Structures, Mohamed A. El-Reedy (2008)
Reinforced Concrete Designers Handbook, 10th Ed Reynold & Steedman
Engineering Concrete Mix Designs & Test Methods, Irving, 1999
Advanced Concrete Technology Vol. #1 Constituent Materials, Newman & Choo, 2003
Advanced Concrete Technology Vol. #3 Processes, Newman & Choo, 2003
Advanced Concrete Technology Vol. #4 Testing & Quality, Newman & Choo, 2003
ACI 201.2R-01 Guide to Durable Concrete
Reinforced Concrete Design Theory & Examples, Macginley, 2003
Masonry and Concrete for Residential Construction, Beall, 2004
ASTM Steel Handbook, 3rd Ed, Bringas, 2002
Reinforcement for Concrete — Materials & Applications, ACI Educational Bulletin #2, 2006
ACI 506R - Guide to Shotcrete
Other Standards REQUIRE additional protection
Though
one may be comfortable with the low permeability of 9,000 psi concrete,
other trade standards specify the use of waterproof membranes (e.g. TCNA,
CTIOA). Ignoring these other standards is as egregious as shooting a
2,500 psi pool shell!
Both TCNA and CTIOA
require additional waterproofing measures under tile in vessels, tubs,
showers, etc. Until those standards are repealed or modified, one
cannot simply chose to ignore them.
Special Protections
The mere use of high density concrete does
not provide protection from hydrogen sulfide or chloride corrosion of
the concrete.
Protection from these ravages of nature can only be
provided with special mix designs, concretes, admixtures and/or
waterproof membranes.
The currently accepted ACI permeability tests have inherent
flaws. The chloride ion penetration test (ASTM
C1202) does not measure how rapidly the ions penetrate the concrete. Nor does the
test account for variations in hydrostatic pressures, a variable that
increases the permeability as the hydrostatic pressures increase. This is why this test is only used to test mix designs in a laboratory.
Through proper mix design and compressive strengths, one can deliver a low value of chloride
ion penetration. However, there is no test available that allows one to demonstrate the in place
chloride ion resistance. This testing is beyond the scope of the current ACI 318, which is the controlling document of most Building Codes and the IBC.
Waterproofing is a required trade practice
WATERPROOFING is also required to protect
concrete and it's steel reinforcement from sulfates, hydrogen sulfide and
chloride degradation. To prevent water from permeating through concrete basements and subterranean structures, waterproofing is oftentimes applied to the soils
prior to the placement of reinforcement or to the outside of
subterranean concrete structure prior to back-filling.
Just because a swimming pool has water intentionally added to the interior of the structure, does that mean that we do not have a duty to protect the concrete from the permeation of water from BOTH sides of the structure?
Paolo Benedetti